Rockwell Automation Publication 1608P-IN003A-EN-P - September 2013 17
Chapter 5
Specifications and Dimensions
Table 2 - Technical Specifications 200 A ProDySC
Electrical Input/Output (Normal Mode—Static Switch)
Connection Configuration
Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load
Standard Input Voltages
3-phase: 208, 380, 400, 415, 480V
1
Voltage Range
± 10%
Current Overload (Static Switch)
150% @ 30Sec., 400% @ 5 Sec., 600% @ 0.5 Sec.
Frequency
50/60 Hz Auto Sensing
Frequency Range
48 -62 Hz
TVSS
Output SPD, 25kA/mode. Protects L-L & L-G on all models; L-N & N-G (4-wire models)
Efficiency
> 99% @ 480V
Electrical Output (Sag Correction Mode - Inverter)
Output Voltage
Pre-sag rms voltage
Voltage Regulation
± 5% typical, +5 % / -13% of nominal max
ProDySC Output Current
200 ARMS
2
Not rated for DC loads; max. allowable 2% DC loading
Crest Factor (at nameplate rms load)
1.45
Voltage Waveform
Sine wave
Voltage Sag Correction Times
Single Event
3 phase 87% to 50% Voltage Remaining 5 seconds
All three phases to zero voltage remaining 3 cycles, based on nameplate ratings with a power factor of 0.7, and frequency of 60Hz
Multiple Event
Max Sag Correction Time 5 seconds cumulative usage
Sequential Sag Recovery 0 seconds (assuming cumulative run-time available)
Full Recovery Time Max 5 minutes
Mechanical
Enclosure Ratings
NEMA 1 (IP20)
Cable Entry
Top or Bottom
Cooling
Filtered Forced Air
Access
Front for servicing and connections
Audible Noise
less than 60 dBA at 1m
Weight
1470 lb (667 kg)
Environmental
Ambient Temperature 0 to 40°C
Storage Temperature -40°C to 75°C
Relative Humidity 0 to 95% non-condensing
Altitude Rated current available to 1000m (3300ft). De-rate output current 10% per 1000m, from 1000m to 3000m (9900ft).
Safety and Compliance
Agency Approvals cULus Listed (UL 1012)
Standards Compliance Exceeds SEMI F47 Standard; IEEE Std C62.41.1 and UL 1449 3rd Ed. compliant
1. ProDySC has not been evaluated for use in Corner Grounded or Ungrounded Delta Power Systems in systems rated over 240V.
2. When using ProDySC with motor drive loads, either insert 3% to 5% line reactance at ProDySC output or limit motor drive loads to 60% of ProDySC rating