ControlNet Fiber-optic Ring Repeater Modules 27
Rockwell Automation Publication 1786-IN003D-EN-P - April 2011
2. Connect the receive port (RX) and transmit port (TX) at the
starting module.
3. Do the following to attach the cable connector to the module connector.
a. Align the key of the cable connector with the slot in the module
connector, and insert the connector into the RX port.
b. Push and twist the locking cap until the bayonet lug is locked into
place.
4. At the second module, connect the cables in reverse.
For example, tracer to TX port on module 1, non-tracer to RX port on
module 1: tracer to RX port on module 2, non-tracer to TX port
on module 2.
ATTENTION: Under certain conditions, viewing the optical port
may expose the eye to hazard. When viewed under some
conditions, the optical port may expose the eye beyond the
maximum permissible exposure recommendations.