34 ControlNet Fiber-optic Ring Repeater Modules
Rockwell Automation Publication 1786-IN003D-EN-P - April 2011
Environmental Specifications - 1786-RPFRL/B, 1786-RPFRXL/B
Attribute 1786-RPFRL/B, 1786-RPFRXL/B
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat)
5...95% noncondensing
Vibration
IEC60068-2-6 (Test Fc, Operating)
5 g @ 10...500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges