1 Publication 2500-IN003A-EN-P—August 2007
Instructions
CENTERLINE
®
2500 Motor Control Centers
IP54 Sealing Instructions
For IP54 structures only
Procedure
1. Remove the tube of caulking (mastic) sealer from the splice kit. Cut the
nozzle at the first notch, 3 mm (1/8”) from the end.
2. Read the application directions on the tube. Apply a continuous bead of
caulking, 3 mm (1/8”) wide, around the outside edge of the sideplate of
the fixed motor control center.
See Figure 1.
Figure 1 Correct Application of Caulking
Apply 3 mm (1/8”) wide
continuous bead of
caulking sealer. Do not
allow “skin” to form on
caulking before joining
the sections.