937CS-AITMP-DC1 Installation Instructions Universal Temperature Converter
9If a current output is operated as a source, the load resistance must be between 0 Ω and 550 Ω (535 Ω if the output format is 4 mA to 20 mA unlimit
10Bul. 937C Universal Temperature Converter Installation InstructionsFDT InterfaceThis manual describes Parameterization mode of the universal temper
11 Communication driverIn a PACTwareTM project, communication with a 937CS-AITMP-DC1 is only possible via thecommunication driver P2P USB FDT. If your
12Bul. 937C Universal Temperature Converter Installation Instructions Measured valueIf you have started the communication between PACTware
13Bul. 937C Universal Temperature Converter Installation InstructionsWarning Simulation If you have started the communication between PACTwareTM a
14Bul. 937C Universal Temperature Converter Installation Instructions DiagnosisIf you have started the communication between PACTwareTM and Bul. 93
15Bul. 937C Universal Temperature Converter Installation InstructionsS• Undervoltage lockout: the supply voltage is too low for the outputs to work pr
16Bul. 937C Universal Temperature Converter Installation Instructions Editing device dataIf you call the parameters for a Bul. 937CS-AITMP-DC1 in PAC
17Bul. 937C Universal Temperature Converter Installation Instructions Please specify the frequency of your supply network (50 Hz or 60 Hz) under Net f
18Bul. 937C Universal Temperature Converter Installation InstructionsMenu InputThe Input tab has the three subordinate tabs I/input, II/input and Ext
1Bul. 937C Universal Temperature Converter Installation InstructionsSymbols UsedThis symbol warns of possible danger. Failure to heed this warning may
19Bul. 937C Universal Temperature Converter Installation Instructions The following parameters can be set:• Sensor (see Connection section):− Resist
20Bul. 937C Universal Temperature Converter Installation Instructions Behavior of the current output of the Bul. 937CS-AITMP-DC1The linear behaviour
21Bul. 937C Universal Temperature Converter Installation Instructions At this setting, the start value of the measurement range is converted to 4 m
22Bul. 937C Universal Temperature Converter Installation Instructions At this setting, the start value of the measurement range is converted to 0 m
Publication 937-IN005A-EN-P - April 2014 (DIR 10001238756)Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A .
2Safety NotesThe Universal Temperature Converter must only be operated by trained personnel in accordance with this handbook.The protection of operati
3Bul. 937C Universal Temperature Converter Installation InstructionsOverviewThe devices of the Bul. 937C IS Barriers, Isolators and Converters are use
4CORRECT: Device snapped on vertically.INCORRECT: Device snapped on from the side. Can damage the contacts and cause the device to fail.Bul. 937C Univ
5Bul. 937C Universal Temperature Converter Installation Instructions20115111118ConnectionThe slip-off terminals significantly simplify connection and
6Bul. 937C Universal Temperature Converter Installation Instructions2-1+2-13+2-1+2-1- 3+ 4+937A-TCJC2-1- 3+2- 3+equal lead resistancesequal lead resis
7Bul. 937C Universal Temperature Converter Installation InstructionsThe remaining black terminals have the following functions (10,11,12 NA):RS 232123
8Bul. 937C Universal Temperature Converter Installation InstructionsIf a current output is operated as a sink, the voltage across the terminals must b