Issue 2 Oct 05 PD-T8031 1
Trusted
TM
Valve Manager
Introduction
The Trusted
TM
Valve Manager package is a Windows based software application that configures,
initiates, collects, processes, and stores valve test information from T8449Trusted
TM
TMR 24Vdc
Valve Monitor” modules.
Features
User configurable valve profiles
Supports manual or automated testing
Records test results for historical trending
Automatic valve discovery
Uses any ODBC compliant data source
Page view 0
1 2 3 4 5 6 ... 49 50

Summary of Contents

Page 1 - Valve Manager

TrustedTM PD-T8031 Issue 2 Oct 05 PD-T8031 1 TrustedTM Valve Manager Introduction The TrustedTM Valve Manager package is a Windows based software ap

Page 2

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 10 1. Description The Valve Manager application is a tool to help manage the valve test functi

Page 3

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 11 2. System Requirements The Valve Manager requires that certain aspects of the systems that

Page 4 - Table of Contents

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 12 It is suggested that all variables associated with a valve adopt the same format, using the

Page 5 - Figures

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 13 Figure 3 Analogue Tags The Valve Manager helps to manage valve testing, but it is the T8449

Page 6 - Tabl es

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 14 Figure 4 DO_TEST board Connect the “_DOS” tags to the odd channels and the “_VPS” tags to

Page 7

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 15 Figure 6 AI_MXIN board Connect the “_DOI” tags to the odd channels and the “_MXD” tags to

Page 8 - Disclaimer

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 16 Figure 8 MXDAT board Connect the “_ETO” tags to the odd channels and the “_ESO” tags to th

Page 9 - Associated Documents

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 17 Figure 10 LINEFLT board 2.2. VTEST Function Block The VTEST function block provides a simpl

Page 10 - 1. Description

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 18 Figure 11 Vtest function block The following table enumerates the possible values of VTM, m

Page 11 - 2. System Requirements

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 19 Figure 12 Installation Type On the following screen, ensure that only the “Libraries” optio

Page 12 - Valve Manager T8031

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 2 Issue Record Issue Number Date Revised by Technical CheckAuthorised by Modificat

Page 13 - 2.1.1. Configuration

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 20 2.2.3. Configuration The VTEST function block must be connected to the appropriate tags in

Page 14

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 21 2.3. Additional Application Logic In addition to the required tags and VTEST function block

Page 15

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 22 The following logic would be used to drive the “_VTP” tag to prevent initiating a test: Fi

Page 16

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 23 Test Error (it sets VTM to 3), then the Valve Manager will reset the VTEST function block b

Page 17 - 2.2. VTEST Function Block

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 24 3. OPC Requirements The Valve Manager application communicates with TrustedTM system throug

Page 18 - 2.2.2. Installation

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 25 On the following screen, ensure that only the “OPC Components” and “Data Access Client” opt

Page 19

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 26 4. Valve Manager Application The TrustedTM Valve Manager package is a Windows based softwar

Page 20 - 2.2.3. Configuration

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 27 When the “OK” button is clicked, the Valve Manager will create an empty database and regist

Page 21

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 28 4.4.1. Project Name The “Project Name” field is used to describe the project within the Val

Page 22

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 29 Use the “Browse Controllers” dialog box to select the specific controller for the project.

Page 23

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 3 This page is intentionally blank

Page 24 - 3. OPC Requirements

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 30 4.4.4. Data Source The “Data Source” field specifies the ODBC data source (i.e. database) w

Page 25 - 3.2. Configuration

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 31 4.4.7. Project Notes The “Project Notes” field is a place to enter a description, comments,

Page 26 - 4. Valve Manager Application

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 32 4.4.9. Saving the Valve Manager Configuration Once the tables have been created, the Valve

Page 27 - 4.4. Creating a Project

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 33 4.5. Working with Multiple Projects The Valve Manager is capable of working with multiple p

Page 28 - 4.4.2. OPC Controller

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 34 4.7. Removing a Project A project can be removed from the Valve Manager’s configuration by

Page 29

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 35 4.8. Adding, Removing, and Renaming Valves Each time the Valve Manager connects to the OPC

Page 30 - 4.4.5. Valve Table Name

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 36 new valves will be display in a separate dialog box, followed by a dialog box for each valv

Page 31 - 4.4.7. Project Notes

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 37 4.9. Configuring a Valve Profile Each valve associated with a project must have a profile.

Page 32 - 4.4.10. Valve Discovery

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 38 4.9.2. State Order The “State Order” dialog box allows you to configure the order in which

Page 33 - 4.6. Editing a Project

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 39 4.9.3. Profile Editor The “Profile Editor” dialog box allows you to configure information t

Page 34 - 4.7. Removing a Project

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 4 Table of Contents 1. Description...

Page 35

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 40 4.10. Applying the Same Profile to Multiple Valves It is possible to apply the same profile

Page 36

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 41 In addition to the “Valve Test” dialog, the progress of a test can be observed in the “Moni

Page 37 - 4.9.1. Profile Strings

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 42 4.14. Controlling the Monitor The Monitor is responsible for communicating with the OPC con

Page 38 - 4.9.2. State Order

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 43 You can specify how often the Monitor polls each OPC controller for valve status informatio

Page 39 - 4.9.3. Profile Editor

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 44 4.16. Main Window The main window displays detail information based on the current selectio

Page 40 - 4.11. Initiating a Test

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 45 4.16.2. Last Test View The Last Test view displays information about the last recorded tes

Page 41

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 46 The overall “Result” field for the test and the individual “Result” fields in the transitio

Page 42 - Issue 2 Oct 05 PD-T8031 42

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 47 4.16.3. Profile View The Profile view displays information about the selected valve’s profi

Page 43 - 4.15. Project Tree

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 48 History Table The History Table view displays information about all of the recorded tests f

Page 44 - 4.16. Main Window

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 49 This page is intentionally blank

Page 45 - 4.16.2. Last Test View

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 5 4.9. Configuring a Valve Profile ...

Page 47 - 4.16.3. Profile View

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 6 Figure 16 Valve Test Permissive Logic ...

Page 48

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 7 Table 1 Tag Naming Convention...

Page 49

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 8 Notice The content of this document is confidential to ICS Triplex Technology Ltd. companies

Page 50

TrustedTM Valve Manager T8031 Issue 2 Oct 05 PD-T8031 9 Revision and Updating Policy All new and revised information pertinent to this document shal