Trusted
TM
PD-T8832
Issue 7 Sep 05 PD-T8832 1
Trusted
TM
60 Channel Analogue
Input FTA
Introduction
The Trusted
T
M
60 Channel Analogue Input FTA T8832 is designed to act as the main interface
between a field device generating a 4-20mA analogue signal and the Trusted
TM
Dual Analogue Input
Module T8432.
Features
60 input channels per FTA.
Industry standard field device connections (2-wire).
Standard DIN rail compatibility.
Simple installation and connection.
24V dc operation.
SmartSlot connection for ‘one to many’ hot replacement of input modules.
Fused field power supply per channel
Page view 0
1 2 3 4 5 6 ... 17 18

Summary of Contents

Page 1 - Input FTA

TrustedTM PD-T8832 Issue 7 Sep 05 PD-T8832 1 TrustedTM 60 Channel Analogue Input FTA Introduction The TrustedTM60 Channel Analogue Input FTA T8832

Page 2

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 10 4.2. PL1 Connections Pin Service 1 24V-1V 2 0V 3 0V 4 24V-2 Table 2 PL1 Connections 4.

Page 3

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 11 4.5. PL4 Connections Pin Service 1 Channel 13 24V dc to field device 2 Channel 13 ret

Page 4 - Tab l e s

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 12 4.7. PL6 Connections Pin Service 1 Channel 25 24V dc to field device 2 Channel 25 ret

Page 5 - Disclaimer

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 13 4.9. PL8 Connections Pin Service 1 Channel 37 24V dc to field device 2 Channel 37 ret

Page 6 - Associated Documents

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 14 4.11. PL10 Connections Pin Service 1 Channel 0 2 Channels 61 Table 11 PL10 Connection

Page 7 - 1. Description

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 15 4.13. PL12 Connections Pin Service 1 Channel 55 24V dc to field device 2 Channel 55 r

Page 8 - 2. Installation

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 16 5. Specifications Field Supply Range 0 to 140V dc Fuses 61-off 50mA Maximum Current (

Page 9 - 4.1. SK1 and SK2 Connections

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 17 This page intentionally blank

Page 11 - 4.6. PL5 Connections

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 2 Issue Record Issue Number Date Revised by Technical CheckAuthorised by Modi

Page 12 - 4.8. PL7 Connections

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 3 Figure 1 T8832 Layout

Page 13 - 4.10. PL9 Connections

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 4 Table of Contents 1. Description...

Page 14 - 4.12. PL11 Connections

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 5 Notice The content of this document is confidential to ICS Triplex Technology Ltd. comp

Page 15 - 4.13. PL12 Connections

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 6 Revision and Updating Policy All new and revised information pertinent to this document

Page 16 - 5. Specifications

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 7 1. Description The TrustedTM 60 Channel Analogue Input FTA T8832 provides termination f

Page 17 - Analogue Input FTA T8832

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 8 2. Installation The TrustedTM 60 Channel Analogue Input FTA T8832 is designed to be mou

Page 18

TrustedTM Analogue Input FTA T8832 Issue 7 Sep 05 PD-T8832 9 4. Assembly Pinout Connections 4.1. SK1 and SK2 Connections The pin connections of SK1

Comments to this Manuals

No comments