Rockwell Automation 1785 PLC-5 User Manual Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
Publication 1785-SG001B-EN-P - June 2006
38 Select Chassis
Mounting Dimensions
(4 in.)
(6 in.)
102 mm 153 mm
51 mm (2 in.)
51 mm (2 in.)
153 mm (6 in.)
(4 in.)
102 mm
(4 in.)
102 mm
153 mm (6 in.)
Area reserved for disconnect,
transformer, control relays, motor
starters, or other user devices.
Wiring Duct
Wiring Duct
Minimum Spacing Requirements for a Remote
I/O and Extended-local I/O Chassis
Mount the I/O chassis horizontally.
Allow 153 mm (6 in.) above and below all
chassis. When you use more than one
chassis in the same area, allow 152.4 mm
(6 in.) between each chassis.
Allow 102 mm (4 in.) on the sides of each
chassis. When you use more than one
chassis in the same area, allow 101.6 mm
(4 in.) between each chassis.
Allow 51 mm (2 in.) vertically and horizontally
between any chassis and the wiring duct or
terminal strips.
Leave any excess space at the top of
the enclosure, where the temperature is
the highest.
102 mm
(4 in.)
153 mm
(6 in.)
51 mm
(2 in.)
102 mm
(4 in.)
Wiring Duct
153 mm
(6 in.)
51 mm (2 in.)
Area reserved for disconnect,
transformer, control relays, motor
starters, or other user devices.
Minimum Spacing Requirements for a
Controller-resident Chassis
Mount the I/O chassis horizontally.
Allow 153 mm (6 in.) above and below the chassis.
Allow 102 mm (4 in.) on the sides of each chassis.
Allow 51 mm (2 in.) vertically and horizontally between
any chassis and the wiring duct or terminal strips.
Leave any excess space at the top of the enclosure,
where the temperature is the highest.
Page view 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 59 60

Comments to this Manuals

No comments