Wiring the SLC Servo Module
Figure 5.2 Equivalent Fast Input Circuit
Figure 5.3 Equivalent Fast Output Circuit
Wiring Hardware
Overtravels
Because the system must go into Estop when a hardware overtravel is
tripped, do the following to the hardware overtravel limit switches of
each axis:
Wire them into the customer Estop string.
Position them outside the software overtravels (see Figure 5.4).