Publication 1758-UM001D-EN-P - June 2011
Installing the Controller 17
Master Control Relay
A hard-wired master control relay (MCR) provides a reliable means for
emergency machine shutdown. Since the master control relay allows the
placement of several emergency-stop switches in different locations, its
installation is important from a safety standpoint. Overtravel limit switches or
mushroom-head push buttons are wired in series so that when any of them
opens, the master control relay is de-energized. This removes power to input
and output device circuits.
Place the main power disconnect switch where operators and maintenance
personnel have quick and easy access to it. If you mount a disconnect switch
inside the controller enclosure, place the switch operating handle on the
outside of the enclosure, so that you can disconnect power without opening
the enclosure.
Whenever any of the emergency-stop switches are opened, power to input and
output devices should be removed.
When you use the master control relay to remove power from the external
I/O circuits, power continues to be provided to the controller’s power supply
so that diagnostic indicators on the processor can still be observed.
The master control relay is not a substitute for a disconnect to the controller.
It is intended for any situation where the operator must quickly de-energize
I/O devices only. When inspecting or installing terminal connections,
replacing output fuses, or working on equipment within the enclosure, use the
disconnect to shut off power to the rest of the system.
ATTENTION
Never alter these circuits to defeat their function since serious
injury and/or machine damage could result.
TIP
If you are using an external DC power supply, interrupt the DC
output side rather than the AC line side of the supply to avoid
the additional delay of power supply turn-off.
The AC line of the DC output power supply should be fused.
Connect a set of master control relays in series with the DC
power supplying the input and output circuits.
TIP
Do not control the master control relay with the controller.
Provide the operator with the safety of a direct connection
between an emergency-stop switch and the master control
relay.