Publication 1769-UM014B-EN-P - May 2010
4-12 Module Data, Status, and Channel Configuration for the Output Modules
Ramping only takes place, if configured, when the output is being commanded
to go to a fault state. Ramping is not done in normal run operation. The ramp
rate values are entered in the Configuration Data file and are accepted as valid
only if:
the number of counts entered for a channel’s ramp rate is greater than or
equal to a minimum of 1% of the total number of full scale counts for
the channel’s selected data format.
See Ramping Types on page 4-11 and 1769-OF4CI Output
Range/Types and Output Data Formats on page 4-11 for minimum
values.
or
the number of counts entered for a channel’s ramp rate may be equal to
0 if ramping is not enabled for the channel.
Table 4.10 1769-OF4VI Output Range/Types and Output Data Formats
Output Data
Format Output
Range/Type
Total Counts in
Full Scale
Number of Counts
for Every 1% of
Ramp Rate
Real Units/Second
for Every 1% of
Ramp Rate
Proportional Counts
-10…+10V 65534 655 0.2V/s
0…5V 0.05V/s
0…10V 0.1V/s
1…5V 0.04V/s
Engineering Units
-10…+10V 21000 210 0.2V/s
0…5V 5750 58 0.05V/s
0…10V 11000 110 0.1V/s
1…5V 4750 48 0.04V/s
Scaled for PID
-10…+10V 16383 164 0.2V/s
0…5V 0.05V/s
0…10V 0.1V/s
1…5V 0.04V/s
Percent of Full Scale
-10…+10V 10000 100 0.2V/s
0…5V 0.05V/s
0…10V 0.1V/s
1…5V 0.04V/s