Configuring the KF3
Chapter 3
32
Displays
Figure 3.1 shows the configuration displays on the bottom of the module.
The left display (one digit) shows the number of the communication
parameter being configured. The right display (two digits) shows the
current setting for that parameter. Communication parameters are
configured in two menus, a main menu, for basic parameters, and a
submenu, for more advanced parameters.
Push Buttons
Figure 3.1 shows three push buttons labelled View, Data, and Exit. The
operation of these buttons is described in Table 3.A.
Table 3.A
Push
Button Operation
Pressing this button or
button combination:
Performs this task:
View In run mode, takes the module into configuration mode.
Note: This is the only button that has a function in run mode.
In configuration mode, cycles through the possible
communication parameters (displayed on the left digit).
If you hold the button down for more than 1 second, the
parameter numbers will advance automatically.
Data In configuration mode, cycles through the possible
communication parameters for the parameter shown on the left.
The data is displayed on the right two digits. If you hold the
button down for more than 1 second, the parameter numbers will
advance automatically.
Exit In configuration mode, from the main menu, returns the module
to run mode without saving any changes. The change in mode
takes effect when the button is released.
From the submenu, returns to the main menu without saving any
changes.
View + Exit In configuration mode, saves all configuration changes, and
returns the module to run mode from either menu. The module
will begin operating with the new configuration as soon as it
returns to run mode.
View + Data In configuration mode, resets all communication parameters
to their factory defaults (see Table 3.B). The changes do not
take effect until the configuration is saved, and the module
returns to run modethat is, until View and Exit are pushed
simultaneously.