DC (10–30V) Output Module4
Publication 1771-IN036C-EN-P - July 2002
!
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic
discharge, which can cause internal damage and
affect normal operation. Follow these guidelines
when you handle this equipment:
Touch a grounded object to discharge potential
static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component
boards.
Do not touch circuit components inside the
equipment.
If available, use a static–safe workstation.
When not in use, keep modules in appropriate
static–safe packaging.
The Series B 1771-OVN dc output module is a sink output and
requires a source input. A source input provides a positive voltage
path and a sink output provides a path to ground.
You must use this module in a 1771-A1B, -A2B, -A3B, -A3B1,
-A4B or later 1771 I/O chassis. Refer to the table below for
processor compatibility.
Table A Processor Compatibility Chart
System Type Use with Processors:
Local MiniĆPLCĆ2/02 (cat. no. 1772ĆLZ, ĆLZP)
MiniĆPLCĆ2/16 (cat. no. 1772ĆLX, ĆLXP)
MiniĆPLCĆ2/17 (cat. no. 1772ĆLW, ĆLWP)
PLCĆ5/15, Series B and later (cat. no. 1785ĆLT)
Remote (with a 1771ĆASB
remote I/O adapter)
PLCĆ2/20 (cat. no. 1772ĆLP2)
PLCĆ2/30 (cat. no. 1772ĆLP3)
PLCĆ3 (cat. no. 1775ĆL1, ĆL2, ĆL3, ĆL4)
PLCĆ3/10 (cat. no. 1775ĆLP4, ĆLP8)
PLCĆ5/15, Series B and later (cat. no. 1785ĆLT)
Do not place this module in the same I/O chassis as the 1771-IX
thermocouple module. You can use this module in the same chassis
as the 1771-IXE thermocouple module.
The controller or I/O chassis power supply, connected through the
backplane of the I/O chassis, powers the logic circuitry of the output
modules. The maximum current drawn from this supply is 330mA.
PreĆinstallation
Considerations
Calculate Power Supply
Requirements
Page view 3