Publication 1792D-IN015B-EN-P - September 2000
Installation Instructions
ArmorBlock MaXum 2 Input with Alarm/
2 Output Module Series B
(Cat. No. 1792D-2BVA2D)
This ArmorBlock MaXumI/O module (Cat. No. 1792D-2BVA2D) is a
stand-alone 24V dc I/O product which communicates via a
DeviceNet network. The sealed housing of this module requires no
enclosure.
This model has 2 inputs with alarm and 2 outputs. Inputs are 24V dc
automatically configured for PNP (sourcing) or NPN (sinking)
devices. Outputs are also configured for sourcing. Two self-protected
24V dc outputs can provide up to 1.0 amp each. Diagnostic features
included are short circuit, open wire, and no load detection reported
to the point level. Local logic control has been added to the Series B
version of this product.
41453
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - 2 Output Module Series B

Publication 1792D-IN015B-EN-P - September 2000Installation InstructionsArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B(Cat. No. 1792D-2B

Page 2 - Low Voltage Directive

10 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Point indicators for this module

Page 3 - Set the Node Address

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 11Publication 1792D-IN015B-EN-P - September 2000The following table describes lo

Page 4 - Install the Module

12 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Specifications2 Input with Alarm

Page 5

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 13Publication 1792D-IN015B-EN-P - September 2000Dimensions (assembled to base)in

Page 6

14 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Hazardous Location Approval The

Page 7

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 15Publication 1792D-IN015B-EN-P - September 2000Les informations suivantes ne co

Page 8

Publication 1792D-IN015B-EN-P - September 2000 PN 957395-30Supersedes Publication 1792D-5.15 - October 1998 © 2000 Rockwell International Corporation.

Page 9

2 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Package ContentsYour package cont

Page 10

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 3Publication 1792D-IN015B-EN-P - September 2000Install Your ArmorBlock MaXum I/O

Page 11

4 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Refer to the illustration of the

Page 12 - Specifications

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 5Publication 1792D-IN015B-EN-P - September 2000To install the module:.1. Positio

Page 13

6 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Connect the Cord Sets to the MaXu

Page 14 - Hazardous Location Approval

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 7Publication 1792D-IN015B-EN-P - September 2000I/O connectors for this module ar

Page 15 - AVERTISSEMENT

8 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B Publication 1792D-IN015B-EN-P - September 2000Communicate With Your ArmorBlock

Page 16

ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 9Publication 1792D-IN015B-EN-P - September 2000The word/bit definitions are expl