FlexPak 3000 Digital DC Drive
Hardware Reference, Installation
and Troubleshooting
Version 4.3
D2-3404-2
Page view 0
1 2 3 4 5 6 ... 103 104

Summary of Contents

Page 1 - Version 4.3

Instruction ManualFlexPak 3000 Digital DC DriveHardware Reference, Installationand TroubleshootingVersion 4.3D2-3404-2

Page 2

1-2FlexPak 3000 DC Drive Hardware Reference Version 4.31.3 Model NumbersDrive specific data, such as horsepower (or output current), regenerative or n

Page 3 - CONTENTS

Index-2FlexPak 3000 DC Drive Hardware Reference Version 4.3 motorwiring connections, 1-22 to 1-25mounting, 1-1EMC compliance requirements, 1-5moun

Page 4

IndexIndex-3 Jjumper settings, 1-4 to 1-10analog tach voltage and analog tach scale (J14 and J11), 1-8armature current feedback (J18), 1-9enhanced fie

Page 5 - List of Figures

Index-4FlexPak 3000 DC Drive Hardware Reference Version 4.3troubleshootingAC line and power input, 1-1DC motor connections, 1-2OIM, 1-3optional kits,

Page 7 - List of Tables

U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives

Page 8

Introduction to the FlexPak 3000 Drive1-3The drive employs a wireless construction and uses a keypad for drive setup, including parameter adjustments

Page 9 - CHAPTER 1

1-4FlexPak 3000 DC Drive Hardware Reference Version 4.31.6 Optional KitsReliance offers modification kits that broaden the application range of the dr

Page 10 - 150FR4042

Introduction to the FlexPak 3000 Drive1-51.7 Getting Assistance from Reliance ElectricIf you have any questions or problems with the products describe

Page 11 - 1.5 Additional Information

1-6FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 12 - 1.6 Optional Kits

Install and Wire the Drive2-1CHAPTER 2Install and Wire the Drive2.1 Install the Drive - Panel LayoutMinimum clearances must be maintained when the dri

Page 13

2-2FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.2 – Drive Mounting Dimensions (1.5 to 30 HP @ 230 VAC / 3 to 60 HP @ 460 VAC / 7 to 11

Page 14

Install and Wire the Drive2-3Figure 2.3 – Drive Mounting Dimensions (40 to 75 HP @ 230 VAC /75 to 150 HP @ 460 VAC / 265 Amp Rated Output)

Page 15 - CHAPTER 2

2-4FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.4 – Drive Mounting Dimensions (100 to 150 HP @ 230 VAC / 200 to 300 HP @ 460 VAC)

Page 16

Install and Wire the Drive2-5Figure 2.5 – Drive Mounting Dimensions (400 to 600 HP @ 460 VAC)

Page 17 - Install and Wire the Drive

©2004 Rockwell Automation. All rights reserved.The information in this manual is subject to change without notice.Throughout this manual, the followin

Page 18

2-6FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.6 – Integrator Drive Mounting Dimensions (1.5 to 30 HP @ 230 VAC / 3 to 60 HP @ 460 VA

Page 19

Install and Wire the Drive2-7 Figure 2.7 – Integrator Drive Mounting Dimensions (40 to 75 HP @ 230 VAC / 75 to 150 HP @ 460 VAC)

Page 20

2-8FlexPak 3000 DC Drive Hardware Reference Version 4.32.2 Install a TransformerInput transformers step up or step down input voltage and can be eithe

Page 21

Install and Wire the Drive2-92.4 Install the MotorStep 1. Verify that the motor is the appropriate rating to use with the drive.Step 2. Install the DC

Page 22 - 2.2 Install a Transformer

2-10FlexPak 3000 DC Drive Hardware Reference Version 4.3Step 4. Connect a suitable equipment grounding conductor to the motor frame, the transformer e

Page 23 - 2.4 Install the Motor

Install and Wire the Drive2-11Figure 2.8 – Drive Control and Power Ground Point Locations (1.5 to 30 HP @ 230 VAC /3 to 60 HP @ 460 VAC / 7-110 Amp Ra

Page 24

2-12FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.9 – Drive Control and Power Ground Point Locations (40 to 75 HP @ 230 VAC /75 to 150

Page 25

Install and Wire the Drive2-13Figure 2.10 – Drive Control and Power Ground Point Locations (100 to 150 HP @ 230 VAC / 200 to 300 HP @ 460 VAC)

Page 26

2-14FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.11 – Drive Control and Power Ground Point Locations (400 to 600 HP @ 460 VAC)

Page 27

Install and Wire the Drive2-15Figure 2.12 – Integrator Drive Control and Power Ground Point Locations (1.5 to 30 HP @ 230 VAC / 3 to 60 HP @ 460 VAC)

Page 28

ContentsICONTENTSChapter 1 Introduction to the FlexPak 3000 Drive1.1 Store the Drive...

Page 29

2-16FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.13 – Integrator Drive Control and Power Ground Point Locations (40 to 75 HP @ 230 VAC

Page 30

Install and Wire the Drive2-172.5.2 Recommended LugsThe following describes how to interpret lug model numbers used in grounding the drive. Refer to t

Page 31 - 1LG 1 2 03

2-18FlexPak 3000 DC Drive Hardware Reference Version 4.32.5.3 Wire AC Power to the DriveStep 1. Size the AC line supply conductors for the specific dr

Page 32

Install and Wire the Drive2-19Important: The tightening torque in the table applies to the wiring device (stud or terminal board) provided. When an in

Page 33

2-20FlexPak 3000 DC Drive Hardware Reference Version 4.3 Figure 2.14 – AC Line Connection Location (1.5 to 30 HP @ 230 VAC 3 to 60 HP @ 460 VAC / 7-11

Page 34

Install and Wire the Drive2-21Figure 2.16 – AC Line Connection Locations (100 to 150 HP @ 230 VAC / 200 to 300 HP @ 460 VAC)Figure 2.17 – AC Line Conn

Page 35

2-22FlexPak 3000 DC Drive Hardware Reference Version 4.32.5.4 Wire the DC Motor to the DriveStep 1. Size the motor armature circuit conductors for the

Page 36

Install and Wire the Drive2-23Figure 2.19 – DC Motor Field and Armature Connection Locations (40 to 75 HP @ 230 VAC /75 to 150 HP @ 460 VAC / 265 Amp

Page 37

2-24FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.20 – DC Motor Field and Armature Connection Locations (100 to 150 HP @ 230 VAC / 200

Page 38

Install and Wire the Drive2-25Figure 2.21 – DC Motor Field and Armature Connection Locations (400 to 600 HP @ 460 VAC)

Page 39

IIFlexPak 3000 DC Drive Hardware Reference Version 4.33.6 Verify the Correct Direction of Motor Rotation ...

Page 40

2-26FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.22 – DC Motor Connections (CCW Rotation Facing Commutator End Shown)

Page 41

Install and Wire the Drive2-272.5.4.1 Wire Motor Overload ProtectionA software (internal) overload is provided that meets NEC/CEC and UL/C-UL requirem

Page 42 - 2.5.5 Wire the Stop Input

2-28FlexPak 3000 DC Drive Hardware Reference Version 4.32.5.5 Wire the Stop InputThe FlexPak 3000 drive can be stopped by the assertion of a stop inp

Page 43

Install and Wire the Drive2-292.5.5.1 Wire the COAST/STOP Digital InputThe user must provide an external operator-accessible coast/stop pushbutton at

Page 44

2-30FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.24 – Sample Regulator Board Terminal Strip Connection Diagram12341234StartStopRunJogR

Page 45 - Connector

Install and Wire the Drive2-31Figure 2.25 – Location of Regulator Board Terminal StripRS-232Connector

Page 46

2-32FlexPak 3000 DC Drive Hardware Reference Version 4.32.5.6 Wire Optional Devices to the DriveRefer to figures 2.24 and 2.25 and table 2.5 when wiri

Page 47

Install and Wire the Drive2-332.5.6.1 Logic InputsThe logic input circuits can be powered either from the internal +24 volt DC power supply or from an

Page 48

2-34FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 49 - CHAPTER 3

Drive Setup and Adjustment3-1CHAPTER 3Drive Setup and Adjustment3.1 Perform a Power Off InspectionInspect the drive and modification kits for possible

Page 50

ContentsIIIList of FiguresFigure 1.1 – Sample FlexPak 3000 Nameplates ... 1-1Figure 1.2 – Model Num

Page 51 - Drive Setup and Adjustment

3-2FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 3.1 – Control Transformer Locations and Settings (380/415 VAC Drives)3.2.2 Converting a

Page 52 - 3.4 Set Jumpers

Drive Setup and Adjustment3-3Step 4. Re-connect power to the drive.Step 5. Through the OIM, access the NOMINAL AC LINE VOLTS parameter (P.037). Set th

Page 53

3-4FlexPak 3000 DC Drive Hardware Reference Version 4.3Verify that there is no path to ground in either the DC motor armature circuit, the shunt field

Page 54

Drive Setup and Adjustment3-53.4.1 Set the Regulator Type (Jumper J15)J15 determines whether the drive uses speed/voltage or torque/current regulation

Page 55

3-6FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 3.3 – Regulator Board Jumpers3.4.2 Setting Program Protection (Jumper J16)The OIM progra

Page 56 - (Jumpers J14 and J11)

Drive Setup and Adjustment3-73.4.3 Set Field Loss Detection (Jumper J20)The FIELD LOSS DETECT jumper (J20) determines whether or not a fault is genera

Page 57

3-8FlexPak 3000 DC Drive Hardware Reference Version 4.3To use the +10V power supply for the manual reference potentiometer, place the jumper on pins 2

Page 58 - 3.5 Power Up the Drive

Drive Setup and Adjustment3-93.4.7 Set the Analog Auto Mode Reference (Jumpers J12 and J10)The AUTOREF jumpers (J12 and J10) select the type of analog

Page 59 - Adjustments

3-10FlexPak 3000 DC Drive Hardware Reference Version 4.33.4.13 Inspect the Power Unit Jumper (J30)Important: An optional Power Interface module, for

Page 60 - 3.9 Make Final Adjustments

Drive Setup and Adjustment3-11Step 4. After power-up, select ARMATURE VOLT for FEEDBACK SELECT by taking the following path from the main menu to acce

Page 61 - CHAPTER 4

IVFlexPak 3000 DC Drive Hardware Reference Version 4.3Figure 2.25 – Location of Regulator Board Terminal Strip...2-

Page 62 - 4.4 Verify Optional Kits

3-12FlexPak 3000 DC Drive Hardware Reference Version 4.3Step 1. Stop the drive.Step 2. Check the value of the output parameter ARMATURE VOLTAGE (P.289

Page 63 - Troubleshooting/Diagnostics

Troubleshooting/Diagnostics4-1CHAPTER 4Troubleshooting/DiagnosticsThis chapter details troubleshooting and diagnostics information fro the FlexPak 300

Page 64

4-2FlexPak 3000 DC Drive Hardware Reference Version 4.34.3 Verify DC Motor ConnectionsVerify that all DC motor connections are correct.• Recheck all m

Page 65 - CHAPTER 5

Troubleshooting/Diagnostics4-34.5 Check the Regulator LED StatusTwo LEDs on the Regulator board indicate the operating status of the Regulator board.

Page 66

4-4FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 67 - APPENDIX A

Replacement Parts5-1CHAPTER 5Replacement PartsThe spare or replacement parts for drives described in this manual are also listed in Replacement Parts

Page 68

5-2FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 69 - Technical Specifications

Technical SpecificationsA-1APPENDIX ATechnical SpecificationsTable A.1 – Voltage and Current RatingsInput Voltage and Frequency RatingsNominal Voltage

Page 70

A-2FlexPak 3000 DC Drive Hardware Reference Version 4.3Table A.2 – Service ConditionsService Factor 1.0 continuousOverload Capacity 150% of full load

Page 71

Technical SpecificationsA-3Table A.6 – Power Ratings1 (230/460 VAC)1 When applying FlexPak 3000 drives to a power distribution system with KVA capacit

Page 72

ContentsVList of TablesTable 1.1 – Drive Modification Kits ... 1-4Table 2.1 –

Page 73 - APPENDIX B

A-4FlexPak 3000 DC Drive Hardware Reference Version 4.3Table A.7 – Power Ratings1 (380/415 VAC)1 When applying FlexPak 3000 drives to a power distribu

Page 74 - B.2 Selecting the Equipment

Technical SpecificationsA-5Table A.10 – Analog InputsManual Mode Reference PotentiometerExternal Voltage Source5 KΩ minimum±10 VDC (when used for anal

Page 75

A-6FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 76

Compliance with European Union Electromagnetic Compatibility StandardsB-1APPENDIX BCompliance with European UnionElectromagnetic CompatibilityStandard

Page 77 - B.3 Mounting the Equipment

B-2FlexPak 3000 DC Drive Hardware Reference Version 4.3B.2 Selecting the EquipmentIn addition to the drive, you will need the following to install the

Page 78 - L1' L2' L3' E

Compliance with European Union Electromagnetic Compatibility StandardsB-3Table B.1 – AC Mains Filter Model Numbers for 1.5 to 150 HP @ 230 VAC FlexPak

Page 79

B-4FlexPak 3000 DC Drive Hardware Reference Version 4.3B.2.4 Selecting an Operator Control StationIf an operator control station is connected to the d

Page 80

Compliance with European Union Electromagnetic Compatibility StandardsB-5B.3 Mounting the EquipmentMount all electronic and electromagnetic components

Page 81 - B.4 Grounding Requirements

B-6FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure B.2 – 3DF4353 and 3DF4354 Filter DimensionsFigure B.3 – 3DF4355 Filter DimensionsL1 L2 L

Page 82

Compliance with European Union Electromagnetic Compatibility StandardsB-7Figure B.4 – 3DF4357 Filter DimensionsFigure B.5 – 3DF4359 Filter DimensionsL

Page 83 - B.5 Wiring the Equipment

VIFlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 84 - B.5.5 Wiring the Motor

B-8FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure B.6 – Side Mounting the 3DF4359 Filter in the L BracketB.3.3 Mounting the AC Mains Induc

Page 85 - B.5.6 Wiring the Kits

Compliance with European Union Electromagnetic Compatibility StandardsB-9B.4 Grounding RequirementsStar grounding must be used and must provide tradit

Page 86

B-10FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure B.8 – Proper Termination of Screened Cables with a Termination FittingFigure B.9 – Prop

Page 87 - FLEXPAK 3000

Compliance with European Union Electromagnetic Compatibility StandardsB-11Figure B.10 – Ground System and Conduit Screen TerminationThe minimum cross-

Page 88 - F2 F1 A1 A2

B-12FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure B.11 – Dressing Power and Control Wires When the AC power leads must leave the ground p

Page 89 - APPENDIX C

Compliance with European Union Electromagnetic Compatibility StandardsB-13The external motor wiring must be run in a screened cable or continuous cond

Page 90 - Regenerative Drives Only)

B-14FlexPak 3000 DC Drive Hardware Reference Version 4.3B.5.6.3 Pulse Encoder and AC Tachometer Feedback Kits (Model Numbers 907FK0101 and 907FK0301)T

Page 91

Compliance with European Union Electromagnetic Compatibility StandardsB-15Figure B.13 – Typical FlexPak 3000 Wiring for EMC Compliance with Optional

Page 92

B-16FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure B.14 – Typical FlexPak 3000 Wiring for EMC Compliance with Optional Dynamic Braking Kit

Page 93 - AC INPUT

Recommended Parts for Integrator DrivesC-1APPENDIX CRecommended Parts forIntegrator DrivesTable C.1 lists the recommended parts that must be provided

Page 94

Introduction to the FlexPak 3000 Drive1-1CHAPTER 1Introduction to the FlexPak 3000 DriveThe products described in this instruction manual are manufact

Page 95 - APPENDIX D

C-2FlexPak 3000 DC Drive Hardware Reference Version 4.3C.1 Wire Inverting Fault Protection to the Drive (S6R, Regenerative Drives Only)The AFB termina

Page 96

Recommended Parts for Integrator DrivesC-3Figure C.1 – Integrator Drive AC Line Connection Locations (1.5 to 30 HP @ 230 VAC / 3 to 60 HP @ 460 VAC)4

Page 97 - Glossary Of Terms

C-4FlexPak 3000 DC Drive Hardware Reference Version 4.3Figure C.2 – Integrator Drive AC Line Connection Locations (40 to 75 HP @ 230 VAC / 75 to 150 H

Page 98

Recommended Parts for Integrator DrivesC-5C.2 Wire Control Power to the Drive Connect the user supplied 115 VAC supply to terminals 188 and 189 of the

Page 99

C-6FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 100

Glossary Of TermsD-1APPENDIX DGlossary Of Termsaltitude: The atmospheric altitude (height above sea level) at which the motor or drive will be operati

Page 101

D-2FlexPak 3000 DC Drive Hardware Reference Version 4.3inertial load: A load (flywheel, fan, etc.) which tends to cause the motor shaft to continue to

Page 102

Glossary Of TermsD-3service factor (SF): When used on a motor nameplate, a number which indicates how much above the nameplate rating a motor can be l

Page 103

D-4FlexPak 3000 DC Drive Hardware Reference Version 4.3

Page 104

Index Index-1INDEXAAC lineconnection location, 1-18 to 1-211.5 to 30 HP @ 230 VAC 3 to 60 HP @ 460 VAC / 7-110 Amp, 1-20100 to 150 HP @ 230 VAC / 200