Connecting program parameters Chapter 1
Safety program to safety program connection rules
The following table summarizes the rules for using program parameters to connect
two safety programs.
Tip:
The connection rules for programs also apply to Equipment Phases.
Program_A
(Safety)
Program_B
(Safety)
Input Output InOut Public
Controller Scope
Tag (Safety Class)
Input
Yes Yes Yes
Output
Yes Yes* Yes Yes
InOut
Yes* Yes Yes
Public
Yes Yes Yes Alias
Controller Scope
Tag (Safety Class)
Yes Yes Yes Alias Alias
* An InOut parameter can only be connected to an Output parameter if the
InOut parameter is configured as a constant.
An Input parameter from Program_A can connect to an Output parameter
of Program_A (wrap around).
Safety mapping must be used to connect standard class tags to safety class
tags/parameters.
Standard class tags cannot alias safety class tags.