ICS Regent
®
PD
-
6031
Industrial Control Services
1
Monitored Digital Input Modules
24 VDC
(T3411)
Issue 1,
March, 06
Monitored digital input modules provide input sensing for 16
field input devices. With a line monitor device installed at the
field switch, monitored digital input modules detect input
switch status and field wiring open and short circuits. Input
and line status are reported back to the controller for use in
application program logic.
Features
·
Sixteen input points.
·
Fault tolerant operation when connected in parallel with
another module of the same type.
·
Hot
-
replaceable.
Complete, automatic testing of all input circuits.
Automatic line monitoring detects open and short field wiring
faults.
·
Individual front panel indicators on each module show the
module’s active/fault and power status, as well as input status
and line fault status for each point.
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5.
The input module circuits are completely and automatically
tested, providing a fail
-
safe interface for safety
-
critical inputs.
Two or three monitored digital input modules can be
connected in parallel to obtain fault tolerant input sensing.
In these fault tolerant configurations, a failed module can be
removed and replaced without interrupting the input signals.
Page view 0
1 2 3 4 5 6 ... 25 26

Summary of Contents

Page 1 - ICS Regent

ICS Regent® PD-6031 Industrial Control Services 1 Monitored Digital Input Modules 24 VDC (T3411) Issue 1, March, 06 Monitored digital input modules

Page 2 - Module Operation

Monitored Digital Input Modules (T3411) 10 Industrial Control Services Figure 5. Fault Tolerant Monitored Digital Input Modules Connected to

Page 3 - Testing and Diagnostics

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 11 The field power supply voltage is regulated to 24 Vdc inside the module. This power is

Page 4

Monitored Digital Input Modules (T3411) 12 Industrial Control Services Figure 6. Module Wiring, Single Sensors to a Single Monitored Digital I

Page 5 - Front Panel Indicators

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 13 Figure 7. Module Wiring, Single Sensors to Redundant Monitored Digital Input Module

Page 6

Monitored Digital Input Modules (T3411) 14 Industrial Control Services Line Monitoring The Monitored digital input module can perform line monitor

Page 7

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 15 Figure 9. Line Monitoring, Single Switch Connected to Redundant Modules. With the l

Page 8 - Application

Monitored Digital Input Modules (T3411) 16 Industrial Control Services Keying The I/O chassis can be physically keyed to prevent accidental damage

Page 9

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 17 Table 2. Slot Key Positions. Module Upper Connector Lower Connector T3411 4 7 Configu

Page 10 - Field Wiring

Monitored Digital Input Modules (T3411) 18 Industrial Control Services 3) Define the Input Module Fields and Thresholds: With the cursor at the t

Page 11

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 19 inputs with the standard (T0412 and T0413) line monitor devices installed. If non-stan

Page 12 - Industrial Control Services

Monitored Digital Input Modules (T3411) 2 Industrial Control Services The module requires connection to a field power supply voltage, ranging fro

Page 13

Monitored Digital Input Modules (T3411) 20 Industrial Control Services During operations the input circuit is monitored for open circuit and short

Page 14

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 21 Field wiring open circuit or short circuit conditions are referenced in the application

Page 15

Monitored Digital Input Modules (T3411) 22 Industrial Control Services In this example, IN1A and IN1B represent the input variables from two redun

Page 16

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 23 result will remain off, eliminating a nuisance trip. Automatic testing of the input mo

Page 17 - Configuration

Monitored Digital Input Modules (T3411) 24 Industrial Control Services If energize-to-trip inputs are used in safety critical applications, line m

Page 18

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 25 Intrinsic Safety External barrier, if required. (requires threshold adjustment, see pa

Page 19

Monitored Digital Input Modules (T3411) 26 Industrial Control Services

Page 20 - Programming

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 3 wired back to the field power supply return. Optionally a line monitor device can be c

Page 21

Monitored Digital Input Modules (T3411) 4 Industrial Control Services Each type of module has a unique identification code that is read by the co

Page 22

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 5 If the I/O processors detect a faulted input circuit, an I/O module fault is indicated

Page 23 - Safety Considerations

Monitored Digital Input Modules (T3411) 6 Industrial Control Services green ACTIVE indicator flashes at the controller's scan rate. If a mo

Page 24 - Specifications

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 7 Figure 2. Monitored Digital Input Module.

Page 25

Monitored Digital Input Modules (T3411) 8 Industrial Control Services Application Simplex Configuration Monitored digital input modules provide a

Page 26 - (T3411)

Monitored Digital Input Modules (T3411) PD-6031 Mar-06 9 Figure 4. Fault Tolerant Monitored Digital Input Modules Connected to a Single Se