Rockwell-automation T71xx Regent+Plus Processor Modules 110 VAC, 220/2 User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 15
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
Processor Modules (T7110, 11, 12, 20, 21, and 22)
6 (Issue 1) Industrial Control Services
Processor Indicator
This red and green LED pair indicates the overall health of the
processor module. During normal operation the green PROC
indicator is on. If a module fault occurs the red indicator turns on
and the green indicator turns off.
Communications Indicator
This red and green LED pair indicates the overall health of the
system’s communications. During normal operation the green
COMM indicator is on. If a communications fault occurs the red
COMM indicator turns on and the green COMM indicator turns
off.
I/O Indicator
This red and green LED pair indicates the overall health of the
system’s I/O. During normal operation the green I/O indicator is
on. If an I/O fault occurs the red I/O indicator turns on and the
green indicator turns off.
An I/O module failure causes all of the processor modules to
indicate an I/O fault. An I/O transceiver module, I/O power
supply module, or I/O Safetybus cable fault causes only the
associated processor module to indicate an I/O fault.
Run Indicator
This green LED is off if the Regent has cold-started (system power-
up without 2oo3 validated programs). After the RAMcode is
loaded the Run LED flashes slowly (about ½ Hertz). With at least
one program loaded and running this indicator will flash faster
(about 2 Hertz).
The RUN indicator will be on steadily when an application
program scan exceeds the maximum allowable scan time
(approximately 200 milliseconds for the 128 kbyte modules, and
400 milliseconds for the 512 kbyte modules).
Battery Indicator
The green BATT OK indicator shows whether the module’s battery
has sufficient power to maintain the programs in the processor. If
the battery has adequate power, this LED will be on. If the battery
needs to be replaced this LED will be off .
Memory Lock Indicator
This green LED indicates whether the module’s memory lock
keyswitch is in the on or off position. The MEMLK indicator will
be green when the keyswitch is in the on position.
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 14 15

Comments to this Manuals

No comments