Rockwell-automation T7835 ICS Regent+Plus Software Validation Package User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 14
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
Software Validation Package for Winterpret (T3835)
PD
- 7
045
March, 06
7
Table
1
.
Failure Modes and Effects Analysis of Application Program
Creation and Download Path.
Failure Mode (due
to random or
systematic faults)
Method of Detection
for GPL Templates
Editing / entry error
Mis
-
compare of Echo
File
to original template
specification
Source File corrupted
CRC error upon attempt
at source file retrieval,
&/or mis
-
compare of
Echo File to original
template specification
Compiler error
Mis
-
compare of Echo
File to original template
specification
Download corruption
Mis
-
compare of Echo
File to original template
speci
fication
Application alteration
due to Regent
memory error
Caught by triplicated
voting / processing of
data
Software Installation
The Software Validation Package is installed on the PC
running the WINTERPRET
application software. The
W
INTERPRET base package provides the necessary installation
software to install this add
-
in validation package. The
validation package should be installed at the same time or
after you have installed the WINTERPRET
base pa
ckage.
Installation Procedure
The files on the validation package diskette are in compressed
form. You cannot simply copy the files to your hard drive
they must be decompressed before they will run. You must
have the WINTERPRET base package distribution disk in order
to run the setup procedure to install the validation package.
To install the Software Validation Package, use the following
sequence:
Important!
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Comments to this Manuals