POINT I/O 4 Channel Analog Current Output Module 15
Publication
1734-IN034B-EN-P - November 2010
Interpret the Status Indicators
Indicator State Description
Module
Status
Off No power applied to device
Green Device operating normally
Flashing green Device needs commissioning due to configuration
missing, incomplete or incorrect.
Flashing red Recoverable fault.
Red Unrecoverable fault may require device replacement
Flashing
red/green
Device is in self-test
4-20mA
Analog
Output
Module
Status
Network
Status
1734
OE4C
0
1
2
3
NODE:
Module status
Network status
Status of output 0
Status of output 1
Status of output 2
Status of output 3
44352
Comments to this Manuals