16 Input/16 Output Digital and 2 Input/2 Output Analog Embedded I/O Boards 17
Publication 1799-IN011A-EN-P - February 2007
Configure the Parameters
The 1799 I/O boards have parameters that are configurable through a DeviceNet
configuration tool such as RSNetWorx for DeviceNet software. The DeviceNet
configuration tools require an Electronic Data Sheet (EDS) for the 1799 I/O boards to
configure the module’s parameters. Find the EDS files at http://www.odva.org
.
Use the descriptions in the following table to help you configure the parameters.
The DeviceLogix capable boards, 1799-D16U16BAGL and 1799-D16U16VAGL, have
additional parameters, which are described in the DeviceLogix User Manual, publication
number ACIG-UM001, and in the Embedded I/O for DeviceNet Technical Data,
publication number 1799-TD001.
Parameter Description
AutoBaud Enables the board to match the network’s communication
rate. When enabled, Baud Rate parameter is ignored.
Input Off-to-On Filter Time Controls the amount of time the input must be in the on
state before the board reports the input as on.
Input On-to-Off Filter Time Controls the amount of time the input must be in the
off-state before the board reports the input as off.
Output Idle State Controls the state of each output when the DeviceNet
master is in an idle-state.
Output Fault State Controls the state of each output when the board loses
communication with the DeviceNet master.
Output Idle Value Controls the value that outputs will have when the output
idle-state is set to use idle value.
Output Fault Value Controls the value that outputs will have when the output
fault-state is set to use fault value.