  • Rated. / 5. Based on customer reviews
Page view 0
BROWN
(+) L1
BROWN (+) L1
BLUE (–) L2
BLACK (N.O.)
WHITE (N.C.)
Electrical Connections: 10-40V DC & 20-30V AC,
100-240V AC
Specifications (relay output)
Touch Button and Guard Installation
(Bulletin 800Z)
1
2
5
4
2
3
1
4
Mini QD (30.5mm)
#889N-F5AE-6F
#889N-F5AE-12F
#889N-F5AE-20F
#889N-R5AE-6F
#889N-R5AE-12F
#889N-R5AE-20F
Micro QD (22.5mm)
#889D-F5AC-2
#889D-F5AC-5
#889D-F5AC-10
WHITE
(1 N.C.)
BLUE
(–) L2
BLACK
(1 N.O.)
BLACK
(1 N.O.)
BROWN
(+) L1
BLUE
(–) L2
WHITE
(1 N.C.)
Cable Option Quick Disconnect (QD) Option
Input Voltage: 10-40V DC, 20-30V AC (800Z-GL...)
Protection: Type 4/4X/13, IP66,1200 psi Washdown
Output Rating:
Min. Load: 6mA, 12V
Operation
1. When the power LED is green, the Touch Button is ready for operation.
2. To enable an output, simply place palm or fingers onto ergonomically contoured surface (see Fig. 1).
3. Touch Button output stays activated as long as the sensor surface remains touched.
4. When the output LED is red, the output is de-energized. When the output LED is green,
the output is energized.
Diagnostics
Code 1: The Power/Fault LED (see Figure 2) will turn red for 1 second during power-up. After the unit
self-diagnostics have passed, the Power/Fault LED will turn green and the Output LED will turn red. If
a fault occurs, the Power/Fault LED will remain red.
Code 2: If the device is touched during power-up, the Power/Fault LED will flash red indicating the
device has been disabled. It will continue to flash until power is cycled to the unit.
Code 3: If the unit detects an unacceptable level of noise, it will become disabled and the
red Power/Fault LED will flash until the noise subsides.
Code 4: If conductive films deposit on the sensor surface over time or if a person attempts to defeat
the sensors with foreign objects, the red Power/Fault LED will flash. The fault will disable the unit and
it will remain disabled until the fault is cleared. (fast flash)
Note: In most applications, the grounded neutral line and/or parasitic capacitance between the input
power leads and earth provide(s) sufficient impedance for the device to function properly. If the unit
powers up normally without diagnostic fault codes but does not activate, the power source could be
ungrounded. For additional information, please contact Rockwell Automation Technical Support by
email at [email protected] or by phone at 440-646-5800.
Figure 1 Figure 2
Sensor Surface
Output LED
Power/Fault LED
CODE TYPE
CODE 2 POWER-UP SAFETY
NOISE DETECTIONCODE 3
DESCRIPTION
FAULT LED FLASH
SEQUENCE
MARGIN DETECTIONCODE 4
• • • • • •
• • • • • • • • •
• • • • • • • • • • • •
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Protect cables
from mechanical damage during installation and use.
ATTENTION: The 800Z touch button is designed to be an ergonomic replacement for a palm button. It is not a safety
device by itself. This product may cause personal injury or property damage if not installed and used in accordance with
the manufacturer's instructions provided as well as applicable standards and regulations. The user has responsibility to
ensure that all local, state, as well as, national laws, codes and regulations relating to the use and installation of this
device are satisfied. Furthermore, safety relays should be used in all two-hand control applications. Some U.S. standards
applicable to two-hand control systems include: ANSI B11, NFPA 79, and ANSI/RIA R15.06. Some European standards
applicable to two-hand control systems include: EN 574, EN 999, EN 60204-1, EN 292-1 and EN 292-2.
ATTENTION: This product has undergone a series change from series B to C. Series C product is RoHS compliant.
Agency Certification:
UL, cUL, and CE compliant for all applicable directives.
CE directives include EN 61000-6-2, EN 50081–2,
and EN 60947–5–1. This product is intended for use in an
industrial environment.
Response Time: Off Time Delay: 60 ms (max.)
On Time Delay: 76 ms (max.), 60 ms (avg.)
800Z-GF3
POWER/FAULT OUTPUT
Cat
C
Ser
5-Pin Molded Cordsets
Mini QD (30.5mm) Micro QD (22.5mm)
GRAY (COMMON)
3
GRAY
(COMMON)
5
GRAY
(COMMON)
100-240V AC (800Z-GF...)
Inductive: C300, AC-15, I
th
=2.5A
R300, DC-13, I
th
=1.0A
Resistive (connector option): 4A, 250V AC
4A, 24V DC
Resistive (cable option): 3A, 250V AC
3A, 24V DC
Overcurrent protection shall be provided: 3A, 250V
129.3mm
(5.09")
111.9mm
(4.40")
69.8mm
(2.75")
42.3mm
(1.67")
81.6kg (180 lbs) MAX
Maintenance
Unit has no customer serviceable parts.
1 SIDE PRINTED,
BODY STOCK WHITE,
BODY INK BLACK
8-1/2" x 11"
4-1/4 x 2-3/4"
PN-54018
FLAT FOLDED
SIZE
MATERIAL
SUPR.
MAT.
NO.
Cable should be protected
Remove Ring For
30mm Mounting
Not Used
on 22mm Mounting
1 - 4mm (0.04"- 0.16") With Guard
1 - 9.5mm (0.04"- 0.37") Without Guard
Installation
Guard 800Z-G3AG_
22.3mm (0.878") 800Z-G_2_ _
30.5mm (1.200") 800Z-G_3_ _
2.8 Nm (25 LB-IN) 800Z-G_2_ _
3.9 Nm (35 LB-IN) 800Z-G_3_ _
800Z-G3ALC1
----
MIN. CYCLE TIME
CYCLE POWER REQ.
10 SEC.
1.5 SEC.
BUL. 800Z TOUCH BUTTON AND GUARD INSTALLATION
GP RELAY VERSION INSTRUCTION SHEET
(ENGLISH)
10000071388 01
M. GUELMI 03-17-10
1 1
B
DIR 10000071388 (Version 01)
Printed in U.S.A
PN-54018
Page view 0
1

Summary of Contents

Page 1 - 10000071388 01

BROWN(+) L1BROWN (+) L1BLUE (–) L2BLACK (N.O.)WHITE (N.C.)Electrical Connections: 10-40V DC & 20-30V AC,