Analog Output Modules
(T3470A)
2
Industrial Control Services
module from affecting module operation). The voted result is
then passed to the I/O bus interface logic.
The voted output data from the I/O bus interface logic is then
used to drive individual digital
-
to
-
analog (D/A) converters per
output channel. The field
-
side D/A output circuits are
optically isolated from the I/O bus interface logic circuits and
receive power from the external power supply.
Each D/A output circuit provides a 4 to 20 mA output current
corresponding to analog output values ranging from 0 to
4095. The analog output circuits are capable of driving
external load devices up to 500 Ohms.
Figure
1
. Block Diagram of Analog Output Module.
Testing and Diagnostics
Each module’s voter circuits are periodically tested by the
processor modules. Discrepant data are sent through one of
three legs of the I/O Safety
bus to determine whether the
module’s voter is able to outvote the incorrect data. A failure