Applying Backup Solutions Increasing system fault tolerance
ControlNet backup module
The ControlNet backup module provides backup of ControlNet I/O.
A secondary controller qualifies critical control information with the
primary controller. Both controllers consume information from
inputs and connect to outputs, but only the primary controller controls
the outputs. The secondary controller establishes control of outputs if
the primary controller shuts down.
The ControlNet backup module provides:
Backing up controller memory
EEPROM memory
You can back up program files using an EEPROM module.
This EEPROM module comes in four sizes:
Options
ControlNet PLC-5
Controller with 1785-CHBM
cartridge installed
PanelView 1000e/1400e
or other
Interface Device
ControlNet PLC-5
Controller with 1785-CHBM
cartridge installed
Redundant ControlNet Network
1794 FLEX I/O
1746 I/O
1771 I/O
AND/
OR
AND/
OR
30371-MC
Feature: Benefit:
high performance, deterministic delivery of I/O data The backup module supports standard features of ControlNet: high-speed data
transmission (5Mbps), user-selectable, deterministic delivery of remote I/O data.
execution of control programs in both the primary
and secondary controller
Both the primary and the secondary controller view remote inputs and continuously execute
their control program. Switchover time is faster because there is no need to crossload data
table information or control programs.
two selectable modes of backup operation Select:
synchronous for a system where both controllers must keep as close as possible to
each other to minimize data table divergence.
asynchronous for a system where application performance, such as program scan
times, must be optimized.
redundant cabling You have the option of wiring a second, or redundant, cable to all remote I/O nodes. Should
one cable break, the second cable will provide continued and uninterrupted transmission.
availability in 1771, 1746 or 1794 platforms Three offerings of I/O to choose or match the type to fit your hot backup application
If you want this amount of backup memory: Select:
16K words 1785-ME16
32K words 1785-ME32
64K words 1785-ME64
100K words 1785-ME100