1-16 Product Overview
Snubbers
Snubbers (resistor/capacitor assemblies) are installed in parallel with
the SCRs, working with the cell reactors to provide adequate voltage
suppression when the SCRs switch off.
Armature-Pulse Transformer Boards
Armature-pulse transformer boards provide the appropriate gate
voltage and current to trigger an SCR. In addition, these boards
provide gate driver isolation from the control logic. Figure 1.11
shows an armature-pulse transformer board.
DC Contactor
The main DC contactor is used to break the DC current to the motor
armature. Coil voltage to the contactor is controlled by contacts from
the pilot relay.
Figure 1.11
Armature Bridge Hardware
J2
J1
Silicon-Controlled Rectifier
(SCR)
Anode
Cathode
Gate
Leads
Armature-Pulse Transformer
Board
Anode
Cathode