12
Publication 284A-QS001C-EN-P - July 2006
ArmorConnect Cable Ratings
The ArmorConnect Power Media cables are rated per UL Type TC
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C or
STOOW 105 °C 600V - CSA STOOW 600V FT2. For additional
information regarding ArmorConnect Power Media see the ArmorStart
User Manual.
Branch Circuit Protection Requirements for ArmorConnect™
Three-Phase Power Media
When using ArmorConnect Three-Phase Power Media, only fuses can be
used for the motor branch circuit protective device, for the group motor
installations. The recommended fuse types are the following: Class CC, T,
or J type fuses. For additional information, see the ArmorStart User
Manual.
Terminal Designations Description Color Code
A1 (+) Control Power Input Blue
A2 (-) Control Power Common Black
PE Ground Green/Yellow
1/L1 Line Power - Phase A Black
2/L2 Line Power - Phase B White
3/L3 Line Power - Phase C Red