Table 10 Fault Types, Descriptions, and Actions (Continued)
See Table 9 for internal drive fault types.
Figure 24 Bulletin 284 ArmorStart
Available only with the Bulletin 284 with sensorless vector control.
No. Fault
Type
Description Action
F48 Params
Defaulted
2 The drive was commanded to write
default values to EEPROM.
1. Clear the fault or cycle power to the drive.
2. Program the drive parameters as needed.
F63 SW
OverCurrent
2 Programmed Parameter 198 [SW
Current Trip] has been exceeded.
Check load requirements and Parameter 198 (SW Current Trip) setting.
F64 Drive
Overload
2 Drive rating of 150% for 1 min. or
200% for 3 sec. has been
exceeded.
Reduce load or extend Accel Time.
F70 Power Unit 2 Failure has been detected in the
drive power section.
1. Cycle power.
2. Replace starter module if fault cannot be cleared.
F80 SVC Autotune The autotune function was either
cancelled by the user or failed.
Restart procedure.
F81 Comm Loss 2 RS485 (DSI) port stopped
communicating.
1. Turn off using Parameter 205 (Comm Loss Action).
2. Replace starter module if fault cannot be cleared.
F100 Parameter
Checksum
2 The checksum read from the board
does not match the checksum
calculated.
Set Parameter 141 (Reset To Defaults) to option 1 Reset Defaults.
F122 I/O Board Fail 2 Failure has been detected in the
drive control and I/O section.
1. Cycle power.
2. Replace starter module if fault cannot be cleared.
LED Status
Indication
Motor
Connector
ArmorPoint
Interface
(Out)
Local Disconnect
2 Outputs
(Micro/M12)
Dynamic
Brake Connector
Source Brake
Connector
010V Analog
Input Connector
ArmorPoint
Interface
(In)
Page view 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 39 40

Comments to this Manuals

No comments