Rockwell-automation 1756-LSP GuardLogix Controller User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
GuardLogix Controllers 13
Publication 1756-IN045E-EN-P - October 2009
To connect a workstation to the serial port, use one of these cables:
1756-CP3 serial cable
1747-CP3 cable from the SLC product
family (If you use this cable, the
controller door may not close.)
If you make your own serial cable:
limit the length to 15.2 m (50 ft).
wire the connectors as shown.
attach the shield to both
connectors.
Controller End
Workstation End
2 RDX
3 TXD
4 DTR
COMMON
6 DSR
7 RTS
8 CTS
9
1 CD
2 RDX
3 TXD
4 DTR
COMMON
6 DSR
7 RTS
8 CTS
9
1 CD
Workstation Controller
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 19 20

Comments to this Manuals

No comments