1-2 Overview
General Description
The 1769-IF4I isolated analog input module converts and digitally stores
analog data for retrieval by controllers, such as the CompactLogix controller or
the MicroLogix 1500 controller. The module supports connections from any
combination of as many as four voltage or current analog sensors. The
1769-IF4I input module provides four, isolated-differential analog input
channels.
The 1769-OF4CI and -OF4VI isolated output modules each provide four,
isolated differential analog output channels.
The modules provide the following input/output types/ranges:
The data can be configured on board each module as:
engineering Units.
scaled-for-PID.
percent.
raw/proportional data.
Hardware Features
The modules contain removable terminal blocks. The modules’ channels are
isolated from each other and are normally wired as differential inputs or
outputs. Single-ended applications can be supported by wiring the negative
terminal of each channel to the other channel’s negative terminals; however,
this eliminates the channel-to-channel isolation provided by the modules.
Module configuration is normally done via the controller’s programming
software. In addition, some controllers support configuration via the user
program. In either case, the module configuration is stored in the memory of
the controller. Refer to your controller’s user manual for more information.
Table 1.1 Normal and Full Ranges
Normal Operating Input Range Full Module Range
±10V dc ± 10.5V dc
1…5V dc 0.5…5.25V dc
0…5V dc -0.5…+5.25V dc
0…10V dc -0.5…+10.5V dc
0…20 mA 0…21 mA
4…20 mA 3.2…21 mA
Page view 9