Rockwell-automation 1771-OVN DC Output Mod. Installation Instructions User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
DC (10–30V) Output Module 7
Publication 1771-IN036C-EN-P - July 2002
!
WARNING
When you connect or disconnect the wiring arm
with field power applied, an electrical arc can
occur. This could cause an explosion in hazardous
location installations. Be sure power is removed
or the area is nonhazardous before proceeding.
!
ATTENTION
Remove power from the 1771 I/O chassis
backplane and field wiring arm before removing
or installing an I/O module.
Failure to remove power from the backplane or
wiring arm could cause module damage,
degradation of performance, or injury.
Failure to remove power from the backplane
could cause injury or equipment damage due to
possible unexpected operation.
Make wiring connections to the module through the field wiring arm
cat. no. 1771-WN. The arm pivots on the I/O chassis to connect with
terminals on the front of the module and acts as a terminal strip. The
wiring arm allows the module to be removed from the chassis
without disconnecting wiring.
!
ATTENTION
The field wiring arm terminal identification
number is not the same as the number of the bit
which controls that output.
I/O Module Groups
Each module condenses two full module groups (32 outputs) into
each I/O chassis slot. For example:
Module group 1 = inputs 00 through 17
Module group 2 = inputs 00 through 17 (module group 2
represents the second set of outputs).
Terminals 1 through 20 represent module group 1. Terminals 21
through 40 represent module group 2. Terminals 10, 20, 30 and 40
are DC common and terminals 1, 11, 21 and 31 are DC power.