Rockwell-automation 1791R-XXXX CompactBlock Distributed I/O on Remote User Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
10 CompactBlock Distributed I/O on Remote I/O Series D
Publication
1791R-IN002B-EN-P - August 2003
1747-SN
Rack
Number
1771-SN
Rack
Number
PLC-2
Rack
Number
PLC-5
Rack
Number
PLC5/250
Rack
Number
PLC-3
Rack
Number
SW1 Switch Position
8 7 6 5 4 3
Rack 62 1 1 0 0 1 0
Rack 63 1 1 0 0 1 1
Rack 64 1 1 0 1 0 0
Rack 65 1 1 0 1 0 1
Rack 66 1 1 0 1 1 0
Rack 67 1 1 0 1 1 1
Rack 70 1 1 1 0 0 0
Rack 71 1 1 1 0 0 1
Rack 72 1 1 1 0 1 0
Rack 73 1 1 1 0 1 1
Rack 74 1 1 1 1 0 0
Rack 75 1 1 1 1 0 1
Rack 76 1 1 1 1 1 0
Not Valid 1 1 1 1 1 1
Rack address 77 is an illegal configuration.
PLC-5/11 processors can scan rack 03.
PLC5/15 and PLC-5/20 processors can scan racks 01-03.
PLC5/25 and PLC-5/30 processors can scan racks 01-07.
PLC5/40 and PLC-5/40L processors can scan racks 01-17.
PLC5/60 and PLC-5/60L processors can scan racks 01-27.
PLC5/250 processors can scan racks 00-37.
Page view 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 35 36

Comments to this Manuals

No comments