Rockwell Automation Publication 23B-IN001K-EN-P - September 2013 49
Chapter 3
Mechanical Installation
This chapter provides information on mounting a PowerFlex 40 Standard
Configured Drive.
Mounting Considerations
Environment
Before deciding on an installation site, verify that the PowerFlex Drive Packages
are not installed in an area where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. The drives are to be installed per the environmental
rating they have been designed for.
Maximum Ambient Air Temperature
PowerFlex 40 Standard Configured Drives are designed to operate at -10° to
40°C (14° to 104°F) surrounding air temperature. The design of the PowerFlex
Standard Configured Drive supports indoor and outdoor applications that are
not in direct sunlight.
Minimum Mounting Clearances
Be sure there is adequate clearance for air circulation around the drive. For best
air movement, do not mount drives directly above each other. Note that no
devices are to be mounted behind the drive. This area must be kept clear of all
control and power wiring.
For information on … See page …
Mounting Considerations 49
Dimensions 50
Layout Drawings 52
ATTENTION: The following information is merely a guide for proper
installation. The Allen-Bradley Company cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or otherwise for
the proper installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are ignored during
installation.