Operating Your PLC-5 Backup System
Chapter 5
5-21
To avoid a control switch from the primary to the secondary processor when
you attempt to edit the ladder program or data table of the primary PLC-5
processor using a programming device:
1. Do not switch the primary PLC-5 processor to REMOTE PROGRAM
mode. Switch the primary PLC-5 processor to REMOTE RUN mode.
Important: If you switch the primary processor to REMOTE PROGRAM
mode, the processor transfers control to the secondary processor. In most
cases, the new primary then switches to Remote Program mode, shutting the
system down.
2. Make edits in the secondary processor first. However, make sure that all
necessary changes are made in both processors.
Important: Using the on-line editing/programming function can cause the
primary and secondary systems to diverge if the system should switch before
you complete the edits in both processors.
This chapter described the basic operation of the 1785-BCM modules and the
PLC-5 backup system, and gave you procedures for operating your module.
Read the next chapter to learn how the backup system operates at switchover,
and how you need to account for this when programming your system.
Editing or Programming
On-line
What to Do Next