Rockwell Automation 1785 PLC-5 User Manual Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 148
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
1785-UM022C-EN-P - February 2008
1-12 Installing Your ControlNet PLC-5 Processor
Specifying the Serial
Interface of Channel 0
Specify RS-232C, RS-422A, or RS-423 communication for Channel
0 by setting the switches of assembly SW2.
Selecting the ControlNet
Network Address of
Channel 2
Select your processors ControlNet network address by setting the
two 10-digit rotary switches on the top of the processor.
You can select from as many as 99 network addresses (from 01 to 99)
for a processor on a ControlNet link. 0 is invalid.
Important: Do not power-up the processor if the processors
ControlNet network address is set to 0. If you do, you
will not be able to communicate with your processor and
your ladder program will be lost, even if you have a
battery installed. If this happens, select a valid network
address for the processor and cycle power.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
Front of processor
Front of processor
Bottom View of PLC-5/20C Processor
Switch Assembly SW2
Bottom View of PLC-5/40C, -5/46C, -5/80C Processor
Switch Assembly SW2
To Specify:
Set Switches:
1 2 3 4 5 6 7 8 9 10
RS-232C
RS-422A
RS-423
Toggle pushed
ON
Toggle pushed
OFF
toward BOTTOM
toward TOP
ON ON ON
OFF OFF
ON ON
OFF
ON
OFF
OFF OFF
ON
OFF OFF OFF OFF OFF
ON
OFF
ON ON ON
OFF OFF
ON
OFF OFF
ON
OFF
00
10
20 30
40
50
60
7080
90
0
1
23
4
5
6
78
9
NET ADDRESS
Network address 01
is shown
For optimum throughput, assign addresses
to your ControlNet nodes in a sequential
order starting with 01.