Configuring the Scanner or Bridge 4-7
After adding the scanner or bridge and the module to the I/O
configuration, you must download the configuration to the controller.
You should also save the configuration to a file on your computer.
1. Select Communications > Download. The Download dialog box
(Figure 4.11) appears.
Figure 4.11 Download Dialog Box
2. Click Download to download the configuration to the controller.
When the download is completed successfully, RSLogix enters
online mode and the I/O OK box in the upper-left part of the screen
is green.
3. Select File > Save. If this is the first time that you saved the project,
the Save As dialog box appears. Navigate to a folder, type a file
name, and click Save to save the configuration to a file on your
computer.
Saving the Configuration
TIP: If a message box reports that RSLogix is unable to go
online, select Communications > Who Active to try to find
your controller in the Who Active dialog box. If it does not
appear, you need to add or configure the EtherNet/IP driver in
RSLinx. Refer to the RSLinx online help.