7-2 Troubleshooting
PORT Status Indicator
Status Cause Corrective Action
Off The module is not powered or
is not connected properly to
the drive.
Securely connect the module to the drive using a
1202-Cxx Communication cable.
Apply power to the module.
Flashing Red The module is not receiving a
ping message from the drive.
Verify that the 1202-Cxx Communication cable is
securely connected.
Cycle power to the drive and/or module.
Solid Red The drive has refused an
I/O connection from the
module.
Another SCANport peripheral
is using the same SCANport
port as the module.
Important: Cycle power to the drive and/or module
after making any of the following corrections:
Verify that all 1202-Cxx cables are securely
connected and not damaged. Replace cables if
necessary.
Verify that the SCANport Host supports Datalinks.
Configure the module to use a Datalink that is not
already being used by another peripheral.
Flashing Green The module is establishing an
I/O connection to the drive.
No action required. Normal behavior if no SCANport
I/O is enabled.
Solid Green The module is properly
connected and is
communicating with the drive.
No action required.
Flashing Red/
Green
The module is performing a
self-test.
No action required.