Publication 1746-RM001A-US-P
12-20 Output Functions
This CALL is implemented as a Protected Typed Logical Write with two address
fields.
Table 12.6 Output Argument
Decimal
Output
Hexadecimal
Output
Description
0 00 Successful Completion.
2 02 Target node cannot accept the message at this time.
3 03 Target node cannot respond because message is too large.
4 04 Target node cannot respond because it does not
understand the command parameters.
5 05 module is off-line (not on link).
6 06 Target node cannot respond because requested function is
not available.
7 07 Target node does not respond.
10 0A module detects illegal target node address.
11 0B module detects illegal file number.
12 0C module detects illegal target file element offset.
13 0D module detects illegal target file length.
14 0E module detects illegal time-out value.
16 10 Target node cannot respond because of incorrect command
parameters or unsupported command.
55 37 Message timed out (time-out value exceeded).
80 50 Target node is out of memory.
96 60 Target node cannot respond because file is protected.
231 E7 Target node cannot respond because length requested is
too large.
235 EB Target node cannot respond because target node denies
access.
236 EC Target node cannot respond because requested function is
currently unavailable.
241 F1 module detects illegal target file type.
250 FA Target node cannot respond because another node is file
owner (has sole file access).
251 FB Target node cannot respond because another node is
program owner (has sole access to all files).