Rockwell-automation 1746-BAS BASIC LANGUAGE User Manual Page 260

  • Download
  • Add to my manuals
  • Print
  • Page
    / 280
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 259
Publication 1746-RM001A-US-P
B-4 BASIC Command, Statement, and CALL Quick Reference Guide
CALL 64 PUSH [string number to be found]
PUSH [base string number]
POP [match position]
Find a string in a string. 15-6
CALL 65 PUSH [new string number]
PUSH [old string number to be replaced]
PUSH [base string number]
Replace a string in a string. 15-7
CALL 66 PUSH [insert position]
PUSH [string number of inserted character]
PUSH [base string number]
Insert string in a string. 15-8
CALL 67 PUSH [base string number]
PUSH [deleted string number]
Delete string from a string. 15-9
CALL 68 PUSH [string number]
POP [number of characters]
Determine length of a string. 15-10
CALL 70 None ROM to RAM program transfer 8-8
CALL 71 PUSH [ROM program number] ROM/RAM to ROM program transfer 8-9
CALL 72 None RAM/ROM return 8-9
CALL 73 None Battery-backed RAM disable 5-1
CALL 74 None Battery-backed RAM enable 5-2
CALL 75 POP [processor mode] Check SLC 500 controller CPU status. 11-7
CALL 77 PUSH [new MTOP address] Protected variable storage 5-2
CALL 78 PUSH [baud rate] Set program port baud rate. 14-2
CALL 80 POP [battery status] Check battery condition. 11-8
CALL 81 None User memory module check and description * 5-3
CALL 82 None Check user memory module map. * 5-4
CALL 84 PUSH [starting word offset in DH485 interface
file]
PUSH [number of words to be transferred]
POP [transfer status]
Transfer DH485 interface file to module input
buffer.
13-19
CALL 85 PUSH [starting word offset in DH485 interface
file ]
PUSH [number of words to be transferred]
POP [transfer status]
Transfer module output buffer to DH485
interface file.
12-17
CALL 86 POP [DH485 interface file remote write status] Check DH485 interface file remote Write
status.
11-8
CALL 87 POP [DH485 interface file remote read status] Check DH485 interface file remote Read status. 11-9
CALL 88 PUSH [number to convert]
PUSH [output buffer to receive converted
value]
Convert BASIC floating-point to SLC
floating-point
9-4
CALL 89 PUSH [input buffer of value to be converted] Convert SLC floating-point to BASIC
floating-point
9-5
Mnemonic Required PUSHes or POPs Description Active In
Command
Mode
Only
Page
Page view 259
1 2 ... 255 256 257 258 259 260 261 262 263 264 265 ... 279 280

Comments to this Manuals