Communicating with Devices on an EtherNet/IP Link 6-35
Total Connections Required by DriveLogix1
The following table calculates the connections used in this example.
Receiving a MSG Instruction
When other devices send messages to the DriveLogix5730 controller, the
path for the message must identify the controller. Configure a CIP-type
message in the originating device. Specify the path the DriveLogix5730
controller as:
Connection: Amount:
connected, cached MSG from DriveLogix1 to DriveLogix2 1
produced tagA
produced from DriveLogix1 to DriveLogix2
other consumer (2 are configured)
1
1
consumed tagB 1
total connections used: 4
xxx.xxx.xxx.xxx,1,1
IP Address
virtual backplane
slot 1