66 Rockwell Automation Publication 7000-UM201B-EN-P - June 2013
Chapter 4 Drive Terminal Application
Unable to Open Program
A device is capable of running multiple terminal sessions, but only if they are to
different drives. Any attempt to run more then one session on the same drive
results in an error message (Figure 67
).
Figure 67 - Unable to Open Program
If this occurs and no other terminal session is evident, the most likely cause is a
previous session which did not close down properly due to some unknown error
condition.
Task Manager on your computer can be used to check for such an occurrence,
typical of that shown in Figure 68
. Look for the application named
Terminal2009.exe” and select ‘End Process.
Figure 68 - Task Manager