Chapter 6 Review Unsupported Features and Implement Workarounds for Migration Issues
10. Configure each state.
a. Select a state.
b. Enter a Value that
matches the state value of
the original cursor list.
c. Select an Access option
for the state.
The default access is
Operator and Remote.
This option provides the
same functionality as the
original cursor list.
Select None for any state
that was a skipped state
in the original cursor list.
d. Repeat a to c for each
state that was in the
original cursor list object.
Access Options Description
Operator and Remote Both the operator and the controller can select the state.
This is the default.
Operator Only an operator can select the state.
Remote The state can only be selected remotely.
None The state cannot be selected. This is equivalent to a
skipped state in the original cursor list.
When the operator scrolls to a skipped state in a
PanelBuilder 1400e application, the list skips past the
state. Because the operator cannot select the state, the
state value is never written to the object’s Cursor
Indicator to PLC connection.
When the operator scrolls to a None state in a FactoryTalk
View ME application, the cursor becomes hollow to
indicate that the state is invalid. Because the state
cannot be selected, the state value is never written to the
object’s Value connection.