Publication 1746-RM001A-US-P
Input Functions 13-9
4.
4.4.
4. The module places the status in the input file word 1, bits 0-7.
5.
5.5.
5. The module sets the input file word 0, bit 10 to inform the SLC processor that
valid data is available.
6.
6.6.
6. The local SLC retrieves the data and status from the buffer and then resets
output file word 0, bit 10 to inform the module that data was received.
7.
7.7.
7. The module resets the input file word 0, bit 10 on the same end of scan cycle
in which the output file word 0, bit 10 was reset.
The SLC processor must not set, then reset, the output file word 0, bit 10 on the
same ladder logic scan cycle. If this occurs, the module may miss the bit being set.
This CALL is active until it is re-executed with different input parameters.
This CALL has ten input arguments and one output argument.
SLC Processor SLC Backplane BASIC or BASIC-T Module
Status Input File
Word 1
Bits 7 through 10
SLC Processor SLC Backplane BASIC or BASIC-T Module
Input File
Word 0, Bit 10
SLC Processor SLC Backplane BASIC or BASIC-T Module
Reset Output File
Word 0, Bit 10
SLC Processor SLC Backplane BASIC or BASIC-T Module
Reset Input File
Word 0, Bit 10