4-8 Module Data, Status, and Channel Configuration for the Output Modules
1769-OF4CI and -OF4VI Channel Configuration
The first two words of each eight word group in the configuration file allow
you to change the parameters of each channel independently. For example,
words 8 and 9 correspond to channel 1 while words 24 and 25 correspond to
channel 3.
Table 4.6 1769-OF4CI and -OF4VI Channel Configuration Word 0
(1)
Define Indicate Bit Settings
1514131211109876543210
Program (Idle) to
Fault Enable
Program (Idle)
Mode Data
Applied
(2)
0
Fault Mode
Data Applied
(2)
1
Hold for
Initialization
Disabled
0
Enabled 1
Program (Idle)
Mode
Hold Last
State
(2)
0
User-Defined
Value
(2)
1
Fault Mode Hold Last
State
(2)
0
User-Defined
Fault Value
(2)
1
Enable Ramping Disabled 0
Enabled
(2)
1
Enable Clamp/
Alarm Latching
Disabled 0
Enabled 1
Enable High
Clamp/ Alarm
Interrupt
Disabled
0
Enabled
(2)
1
Enable Low
Clamp/ Alarm
Interrupt
Disabled
0
Enabled
(2)
1
Enable Channel Disabled 0
Enabled 1
(1)
Refer to the 1769-OF4CI and -OF4VI Output Channel Configuration Word 1 table.
(2)
Hold Last State and User Defined Fault functionality is only supported when the analog module is used in a DeviceNet
application via the 1769-ADN adapter No local configuration, that is, a MicroLogix or CompactLogix system, supports this
functionality. Refer to your controller manual for details.