Module Diagnostics and Troubleshooting 5-7
1769-IF4I Specific
Configuration
Error
X400 010 0 0000 0000 General configuration error; no additional information
X403 010 0 0000 0011 Invalid real time sample rate value
X404 010 0 0000 0100 Invalid input filter selected (channel 0)
X405 010 0 0000 0101 Invalid input filter selected (channel 1)
X406 010 0 0000 0110 Invalid input filter selected (channel 2)
X407 010 0 0000 0111 Invalid input filter selected (channel 3)
X408 010 0 0000 1000 Invalid input range selected (channel 0)
X409 010 0 0000 1001 Invalid input range selected (channel 1)
X40A 010 0 0000 1010 Invalid input range selected (channel 2)
X40B 010 0 0000 1011 Invalid input range selected (channel 3)
X40C 010 0 0000 1100 Invalid input format selected (channel 0)
X40D 010 0 0000 1101 Invalid input format selected (channel 1)
X40E 010 0 0000 1110 Invalid input format selected (channel 2)
X40F 010 0 0000 1111 Invalid input format selected (channel 3)
X410 010 0 0001 0000 Invalid low alarm data value (channel 0)
X411 010 0 0001 0001 Invalid low alarm data value (channel 1)
X412 010 0 0001 0010 Invalid low alarm data value (channel 2)
X413 010 0 0001 0011 Invalid low alarm data value (channel 3)
X414 010 0 0001 0100 Invalid high alarm data value (channel 0)
X415 010 0 0001 0101 Invalid high alarm data value (channel 1)
X416 010 0 0001 0110 Invalid high alarm data value (channel 2)
X417 010 0 0001 0111 Invalid high alarm data value (channel 3)
X418 010 0 0001 1000 Invalid alarm deadband value (channel 0)
X419 010 0 0001 1001 Invalid alarm deadband value (channel 1)
X41A 010 0 0001 1010 Invalid alarm deadband value (channel 2)
X41B 010 0 0001 1011 Invalid alarm deadband value (channel 3)
X41C 010 0 0001 1100 Alarm not enabled (channel 0)
X41D 010 0 0001 1101 Alarm not enabled (channel 1)
X41E 010 0 0001 1110 Alarm not enabled (channel 2)
X41F 010 0 0001 1111 Alarm not enabled (channel 3)
(1)
X represents the Don’t Care digit.
Table 5.4 1769-IF4I Extended Error Codes
Error Type Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary Binary