Rockwell-automation 20-750-PNET2P Profinet Dual Port Option Module User Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
Rockwell Automation Publication 750COM-UM007A-EN-P - January 2013 25
Installing the Option Module Chapter 2
Table 1 - Drive and Option Module Start-Up Status Indications
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see page 56
and page 57.
Item Name Color State Description
Drive STS Indicator
STS
(Status)
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing When running, a type 2 (non-configurable alarm condition exists – drive continues to run.
When stopped, a start inhibit condition exists and the drive cannot be started (see drive
parameter 933 - [Start Inhibits]).
Steady A type 1 (user configurable) alarm condition exists, but the drive continues to run.
Red Flashing A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is
cleared.
Steady A non-resettable fault has occurred.
Red/Yellow Flashing Alternately A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not
enabled, acts like a major fault. When running, the drive continues to run. System is
brought to a stop under system control. The fault must be cleared to continue.
Yellow/Green Flashing Alternately When running, a type 1 alarm exists.
Green/Red Flashing Alternately Drive firmware is updating.
Option Module Status Indicators
PORT Off The option module is not powered or connected properly to the drive.
Red Flashing The option module is not receiving any communication from drive.
Steady The option module detected a duplicate or invalid port ID.
Green Flashing Normal operation. The option module is establishing communication with drive. It will
turn steady green or red.
Steady Normal operation. The option module is properly connected and communicating with the
drive.
Orange Steady The brand of the option module and drive do not match.
MOD Off The option module is not powered or connected properly to the drive.
Red Flashing The option module has failed the firmware test or a firmware update is in progress.
Steady The option module has failed the hardware test.
Green Flashing Normal operation. The option module is operating but is not transferring I/O data to a
controller.
Steady The option module is operating and is transferring I/O data.
NET A
NET B
Off The option module cannot establish network communication or has experienced a
communication timeout.
Red Flashing The option module has detected a network configuration error.
Steady The option module has experienced an internal network controller error (ERTEC 200 Self-
Test failure).
Green Steady Normal operation. The option module is properly connected and communicating on the
network.
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 99 100

Comments to this Manuals

No comments