Configuring the Adapter 3-11
To set the fault configuration parameters
If you set Parameter 07 - [Comm Flt Action] or 08 - [Idle Flt Action]
to the “Send Flt Cfg,” the values in the following parameters are sent to
the drive after a communications fault and/or idle fault occurs. You must
set these parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is not
required.
Changes to switch settings on some adapter parameters require that you
reset the adapter before the new settings take effect. You can reset the
adapter by cycling power to the drive or by using the following
parameter:
Set the Parameter 06 - [Reset Module] to Reset Module:
Figure 3.11 Reset Screen on PowerFlex 4-Class HIM (22-HIM-*)
When you enter 1 = Reset Module, the adapter will be immediately
reset. When you enter 2 = Set Defaults, the adapter will set all adapter
parameters to their factory-default settings. The value of this parameter
will be restored to 0 = Ready after the adapter is reset.
Parameter Name Description
10 Flt Cfg Logic A 16-bit value sent to the drive for Logic Command.
11 Flt Cfg Ref A 16-bit value (0 – 65535) sent to the drive as a
Reference.
Resetting the Adapter
!
ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault when
you reset the adapter. Determine how your drive will respond before
resetting a connected adapter.
Value Description
0 Ready (Default)
1 Reset Module
2 Set Defaults
Reset Module
Parameter: #
006
Ready 0
VAL UE LIMITS SEL !