Rockwell-automation 57C435 Processor Module, AutoMax User Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
3Ć4
3.4 OnĆBoard Battery Replacement
WARNING
THE BATTERY USED WITH THIS DEVICE MAY PRESENT A HAZARD IF
MISTREATED. DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 100_C
(212_F), INCINERATE, OR SWALLOW. REPLACE BATTERY WITH RELIANCE
ELECTRIC M/N 57C385 ONLY. DISPOSE OF USED BATTERY PROMPTLY. FAILURE
TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY
INJURY.
See section 5.2 for a list of the possible reasons that the BAT. OK"
light on the Processor faceplate can shut off. If you need to replace
the battery, the superĆcapacitor will provide a typical 10 hours of
backĆup power between the time the BAT. OK" light goes off and
power is removed from the rack, and the time you insert and activate
the new battery. If you replace the battery within this time limit, you
will not need to reĆload the operating system and application tasks.
Complete battery specifications can be found in Appendix A.
Use the following procedure to replace the battery on the Processor
module.
Step 1. Turn off power to the system. All power to the rack, as well
as all power to the wiring leading to the module, should be
off.
Step 2. Use a screwdriver to loosen the screws holding the
connectors to the module. Remove the connectors from
the module.
Step 3. Loosen the screws that hold the module in the rack.
Remove the module from the slot in the rack, being careful
not to touch the connectors on the back of the module.
Step 4. Take the old battery out of the holder. Remove the tape
from the new battery and insert it in the holder. Make
certain that the battery is facing the proper direction.
Step 5. ReĆinsert the module into the correct slot in the rack. Use a
screwdriver to secure the module into the slot.
Step 6. ReĆattach the connector(s) to the mating half on the
module. Make certain that the connector is the proper one
for this module. Use a screwdriver to secure the connector
to the module.
Step 7. Turn on power to the rack. The module will automatically
execute its powerĆup diagnostics. The green OK" light
should be lit, and the BAT. OK" should be lit. If this
Processor or any Processor in the rack displays code
LO", you will need to reĆload the operating system. See
4.1 for more information.
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 59 60

Comments to this Manuals

No comments