138 RSLogix 5000 Add-On Instruction
8. Enter parameters (operands) for the AOI.
Monitoring and Updating a
Project Online
This section provides instructions on how to:
establish online communication with a Logix controller to
monitor and tune (modify parameters) the fuzzy AOI
what to do if online communication is not working correctly.
The communication with the Logix controller is via a RSLinx
Classic OPC Server.
Before establishing online communication, certain conditions must be
met.
The fuzzy AOI is generated by FuzzyDesigner.
The fuzzy AOI is imported to an RSLogix 5000 project.
An instance of the fuzzy AOI is created in the RSLogix 5000
project.
The RSLogix 5000 project is downloaded to a Logix controller.
The order of parameters correspond to
the port order of the fuzzy project
you can optionally set it from Tools >
Set Port Order menu item in
FuzzyDesigner
The order of parameters correspond to
the port order of the fuzzy project
you can optionally set it by the
Tools > Set Port Order menu item
in FuzzyDesigner