Appendix
A
A-1
Selecting Switch Settings
Make the following switch selections for Classic PLC-5 processors.
1. Regardless of this switch setting, outputs are reset when either of the following occurs:
processor detects a runtime error
an I/O chassis backplane fault occurs
you select program or test mode
you set a status file bit to reset a local rack
2. If
an EEPROM module is not installed and processor memory is valid, the processor
'
s PROC
LED indicator blinks,
and the processor sets S:11/9, bit 9 in the major fault status word.
3. A processor fault occurs if processor memory (solid red PROC LED) is not valid.
4. You cannot clear processor memory when this switch is on
45
2-slot
1-slot
1/2- slot
1
Always
Off
19309
67
Outputs of this I/O chassis remain in their last state when
a hardware failure occurs.
1
Outputs of this I/O chassis are turned off when a
hardware failure occurs.
1
Pressed in
at top ON (closed)
Pressed in
at bottom OFF (open)
EEPROM memory transfer to processor memory at powerup.
2
EEPROM memory transfers to processor memory if processor memory
not valid.
EEPROM memory does not transfer to processor memory
.
3
RAM memory protection disabled.
RAM memory protection enabled.
4
Not allowed
RAM Memory Protection
Switch
8
OFF
ON
EEPROM Transfer
Addressing
Last State
Switch
ON
OFF
Switches
Switches
OFF OFF
OFF ON
ON OFF
ON ON
OFF OFF
ON ON
ON OFF
Chassis Backplane with
Classic PLC5 Processor
Page view 138
1 2 ... 134 135 136 137 138 139 140 141 142 143 144 ... 185 186