Selecting Interrupt Routines
Chapter 7
7-7
In Figure 7.4, #N10:0 is the reference file.
Figure 7.4
Example
of Comparing a Major Fault Code with a Reference
JMP
MOV
MOVE
Source
Dest
S:11
0
RES
R6:0
][
R6:0
FD
10
][LBL
10
Last rung in fault routine
TND
EN
FSC
FILE SEARCH/COMPARE
Control
Length
Position
Mode
R6:0
20
0
ALL
DN
ER
Expression
S:12 = #N10:0
U
R6:0
IN
The processor completes the scan of the fault routine. If the routine clears
S:11, the processor returns to the program file and resumes program
execution. If the fault routine does not clear S:11, the processor executes
the rest of the fault routine and goes into FAULTED mode.
Important: If the fault routine clears the major fault, the processor
completes the fault routine and returns to the next instruction in the
program file that follows the one that contained the faulted instruction.
The remainder of the rung is executed. It appears that the fault never
occurred. The fault routine execution continues until you correct the
cause of the fault.